FCU Basic Model

ボンズ カジノ 入金不要ボーナス

The basic model uses a reheat system. In this system, the aluminum plate sensible heat exchanger (PWT) uses heat energy recovered from warm outdoor air to heat the supplied air.
ボンズ カジノ 入金不要ボーナスhe other hand, the heat energy recovered from the cold air after it passes through the cooling coil is used primarily to cool the warm outdoor air.
Installing the PWT this way reduces the capacity of cooling coils and other components, contributing to overall energy savings.

Features

  1. 1. Low humidity air witボンズ カジノ 入金不要ボーナス dew point temperature of 7 °C can also be supplied.
  2. 2. Cooling and dehumidification from mid-seasボンズ カジノ 入金不要ボーナスo winter humidity.
ボンズ カジノ 入金不要ボーナス

Specificatiボンズ カジノ 入金不要ボーナスable

Supply air dew point temperature: 7 °C (50 Hz/60 Hz)

FCU-431 FCU-112 FCU-222 FCU-332
Rated air volume (m3/ボンズ カジノ 入金不要ボーナスt 20 °C) 430/430 1000/1180 1900/2230 2840/3340
Chiller: Nominal output (kW) 3.0 7.4 14.8 22.2
Chiller: Cooling capacity (kW) 10.4 28.2 53.3 79.8
Chiller: Rated current (A) 13.3/15.4 32.5/37.9 56.4/57.2 84.6/85.8
Reheater: Installed capacity (kW) 2.4 6.3 12.0 18.0
Blower (kW) 0.4 0.75 1.5 2.2
External static pressure (Pa) 300 300 300 300
Dimensions : L×W×H (mm) 1800×1000×1900 2100×1200×1950 2300×1950×2000 3000×2400×2100
Approximate weight (kg) 400 800 1250 1750